IMPORTANT: Figures shown are for non-reversing models ONLY. For reversing models contact the
factory.
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the back side of the upper or top control door. In the case of 208 VAC or
240 VAC, the supply voltage must match the electric service specifications of
the data label exactly.
IMPORTANT: The wire size must be properly sized to handle the related current.
WARNING: 208 VAC and 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or
obligation.
ADG-25V (GAS)
ADS-25V (STEAM)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify
exact voltage.
NOTES: A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/
verify correct breaker size according to appliance amp draw rating and type of
breaker used.
C. Circuit breakers for 3Ø dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
120 2 10 -- 20
208 2 5 -- 15
240 2 5 5 15
208 3/4 3 -- 15
240 3 3 4 15
380-400 3/4 -- 2 15
416 3/4 -- 2 15
460/480 3/4 2 -- 15