ADC AD-95 User Manual Page 26

  • Download
  • Add to my manuals
  • Print
  • Page
    / 92
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 25
26 | Kabeldon low voltage switchgear system 2011 | We reserve the right to alter design and range of our products without prior notice
Switching devices with independent manual operation
SEKO, SEKOD
Designation ID No. Qty modules Rated current Cable connection
Al/Cu
Fits in enclosures Suitable
fuse size
Weight
A mm² kg/each
SEKO 160 2CGX0 63050051 12 160 50-300* KSIK, CDC, SDC NH 00 5
SEKOD 250
2CGX0 63050234 17 224 50–300* KSIK, SDC NH 0, NH 1 5.2
SEKOD 400 2CGX0 63050235 17 355 50–300* KSIK, SDC NH 1, NH 2 8.2
* Max. area refers to connection with a stranded or solid conductor.
To be ordered separately
Designation ID No. Rated current Qty. per pack Weight
A kg/each
ILM 250 2CGX0 63090032 1 0.8
ILM 400
2CGX0 63090034 1 0.6
PSM 250 2CGX0 63090031 1 0.7
KN 00 2CGX0 53190319 160 3 0.1
KN 1 2CGX0 53190345 400 3 0.2
SEKOD 250
Switch-fuse with breaking on both
sides of the fuse. Here SEKOD
250 in OFF position.
ILM 250
Interlocking mechanism for
SEKOD 250.
ILM 400
Interlocking mechanism for
SEKOD 400.
PSM 250
Parallel handle for SEKOD 250.
SEKOD 400
Switch-fuse with breaking on both
sides of the fuse. Here SEKOD
400 in OFF position.
KN 1
Linking knife.
KN 00
Linking knife.
SEKO 160
Switch-fuse with breaking
on both sides of the fuse.
Switch Select
160 A SEKO 160 + KN 00
250 A
SEKOD 250 + KN 1
400 A SEKOD 400 + KN 1
Page view 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 91 92

Comments to this Manuals