40 | Kabeldon low voltage switchgear system 2011 | We reserve the right to alter design and range of our products without prior notice
General accessories
GBLB 45, GBL 63
Designation ID No. Rated data Cable connection Dimensions Weight
Height Width Depth
mm² mm kg/each
GBLB 45 2CGX0 63190371 400 V, 45 A 16/25/4 Cu 250 105 180 2.2
GBL 63
2CGX0 63190374 400 V, 63 A 4Cu/16 Al/Cu 382 250 132 4.8
Maximum lighting loads switched by contactor
(Data coming from the contactor manufacturer)
Lamp type Lamp
Wattage
Lamp
rated
current
230 V
Max Quantity
lamps/phase
W A GBLB 45 GBL 63
High-pressure sodium
Metall-halogen lamps
Uncompensated
150
1,8 17 23
250 3,0 10 14
400 4,4 7 9
600 6,2 5 7
1000 10,3 3 4
High-pressure sodium
Metall-halogen lamps
Compensated
150 1,0 20 50
250 1,5 13 33
400 2,5 8 20
600 3,3 6 15
1000 6,2 3 8
Mercury, high
pressure
Uncompensated
125 1,2 34 55
250 2,2 18 29
400 3,3 12 19
Mercury, high
pressure
Compensated
125 0,7 28 60
250 1,3 15 30
400 2,1 10 18
GBLB 45
Street lighting box for five-wire system (TN-S).
Can be mounted on the PE/PEN-busbar or a mounting plate
Contactor for 45 A
Protection IP2X
Connectable cable cross section:
Incoming cable to terminal block, max. 16 mm²
Outgoing cable from contactor, max. 25 mm²
Incoming/outgoing wiring for control circuits, max. 4 mm²
GBL 63
Street lighting box for five-wire system (TN-S).
Can be mounted on mounting plate in the upper section
of enclosures CDCM and SDCM
Contactor for 63 A
Degree of protection IP3X
7 M (125) free space for kWh metering, control etc
Connectable cable cross-section:
Incoming/outgoing cable to terminal block, max. 16 mm²
Incoming/outgoing wiring for control circuits, max. 4 mm²
Single line diagram for GBLB 45 and GBL 63.