84 | Kabeldon low voltage switchgear system 2011 | We reserve the right to alter design and range of our products without prior notice
Technical data
Busbar system 400 A 630 A 1000 A 1600 A 1600 A 2500 A
CSS
2)
CSS
2)
Rated operational voltage, U
e
V 690 690 690 690 690 690
Rated insulation voltage, U
i
V 1000 1000 1000 1000 1000 1000
Rated conventional thermal current,
I
th
and rated operational current, I
e
A 400 630 1000 1600 1600 2500
Rated short-time withstand current,
I
cw
kA
rms/s
30/0.2
1)
23/1
1)
40/1
1)
70/1
1)
30/1 65/1
Rated fused short-circuit current, I
cf
kA
rms
50 85 50 85
max A 3//315 3//250 3//315 3//250
Rated peak withstand current, I
pk
kA
peak
55 55 67 148
Rated peak withstand current; 1 m
long busbar without fitted device, I
pk
kA
peak
– –5085
Degree of protection according to
IEC 60 529
IP2X IP2X IP2X IP2X IP2X IP2X
1) Test prerequisite: T=100 K. Final temperature of the busbar max. 150° C.
2) Adjusted for use in substations and low voltage switchgears.
Switching device with dependent ma-
nual operation, uninterrupted duty
SLD 000 SLD-FHD 000 SLD 00 SLD-FHD 00 SLD 1 SLD 2 FD 3300
Rated operational voltage, U
e
V 400 690
1)
230 400 690
1)
230 400 690
1)
400 690
1)
1000
1)
400
Rated insulation voltage, U
i
V 690 690 690 690 690 1000 690
Rated impulse withstand
voltage, U
imp
kV 8 8 8 8 8 8 8
Rated operational current, I
e
and rated conventional thermal
current, I
th
2)
A
100 80 100 160 160 160 250 250 400 355 160 400
400
3)
600
3)
Utilization category according to
IEC 60947-3
AC-23B AC-22B AC-21B AC-23B AC-21B AC-21B AC-23B AC-22B AC-23B AC-22B AC-21B AC-21B
Rated short-time withstand
current, I
cw
kA
rm/s
6.1/1
5)
6.1/1
5)
16.2/1
5)
16.2/1
5)
15/1
Rated peak withstand current, I
pk
kA
peak
10.9
5)
10.9
5)
34.4
5)
34.4
5)
42
Rated conditional (fused) kA
rms
50 30 30 50 30 30 50 50 50 50 30 50
short-circuit current, I max A 100 80 100 160 160 160 250 250 400 355 160 2//400
Degree of protection according
to IEC 60529
fuse IP2X 4) IP2X
4)
IP2X
4)
IP2X
4)
IP2X IP2X IP2X
Connectable conductor cross-
section, Cu/Al
mm
2
2.5-95 2.5-95 2.5-95 2.5-95 50-300 50-300 50-300
Remarks
1) To be used only in dry environments.
2) Fuse with power dissipation according to IEC 60269-2-1.
3) With linking knives.
4) IP1X at operation, depending on design dimensions of the fuse.