68 | Kabeldon low voltage switchgear system 2011 | We reserve the right to alter design and range of our products without prior notice
Metered public lighting pillars
GBC 45-2, GBC 63-3
Designation ID No. Qty. modules Rated data Dimensions Weight
Height Width Depth
mm kg each
GBC 45-2 2CGX0 63300632 20 400 V, 45 A 1800 350 220 58
GBC 63-3
2CGX0 63300633 40 400 V, 63 A 1800 600 220 81
SLD 000 2CGX0 63050106 3 400 V, 100 A 495 38 160 1.7
AD 350 2CGX0 63030262 400 A 61 38 45 0.2
ADC 25 2CGX0 63030233 63 A 36 10 26 0.1
Public lighting pillars GBC 45-2, 45 A,
2 groups contain:
Qty Designation Description
1 CDCM 420 Enclosure
1
MPF 63 B Meter panel
1 GBLB 45 Street lighting box
1 PBKP 50 Seal cover
3 AD 95 Insulated connector
2 SLD 000 Fuse-switch disconnector
2 ADC 25 Non-insulated connector
The public lighting pillar is extendable to 3 groups.
The public lighting pillar is extendable to 3
groups.
Qty Designation Description
1 CDCM 440 Enclosure
1
MPF 63 B Meter panel
1 MPP 20 Mounting plate steel
1 GBL 63 Street lighting box
1 PBKP 50 Seal cover
3 AD 95 Insulated connector
3 SLD 000 Fuse-switch disconnector
3 AD 350 Non-insulated connector
The public lighting pillar is extendable to 10 groups.
GBC 45-2
GBC 63-3
Options and accessories
Material when several outgoing groups:
SLD 000
Fuse-switch disconnector. Fuse NH 000 or
C00. Degree of protection IP2X.
AD 350
Non-insulated connector for connecting three
separate conductors, each max 50 mm² Al/Cu.
May only be used with non-protected busbars.
ADC 25
Non-insulated connector. May only be used
with non-protected busbars.
Page view 67
1 2 ... 63 64 65 66 67 68 69 70 71 72 73 ... 91 92

Comments to this Manuals

No comments