We reserve the right to alter design and range of our products without prior notice | Kabeldon low voltage switchgear system 2011 | 41
General accessories
SCA, SVA
Designation ID No. Rated data Cable
connection
Dimensions Weight
Height Width Depth
mm² mm kg/each
SCA 2CGX0 53190270 230 V (L-N) 25 150 130 90 2.9
SV
A 2CGX0 53310671 230 V (L-N) 25 90 90 90 1.9
SCA
Surge current arrester kit. Heavy-duty protection needed
when an overhead line or lightning-conductor is used.
The kit comprises:
Three heavy duty arresters for TN-C (four-wire) system
with bracket for mounting on the PEN bar
The necessary flexible wires
Connectors (AD 95 for phase connection, AD 70 for PEN
connection).
Installation instructions
Choice of surge protection:
Choose SCA (heavy-duty protection)
When the building has a lightning conductor.
Electricity supply via overhead line.
In rural areas with a high frequency of lightning strikes.
Class: I/B
Choice of surge protection:
Choose SVA (medium-duty protection)
With electricity supply via buried cable (at least 200 metres
of cable to the overhead line network).
Class: II/C
SVA
Surge voltage arrester kit.
A medium-duty arrester for use with underground networks
and where no lightning-conductors are used.
The kit comprises:
Four medium-duty arresters for TN-S systems with
attachment for mounting on the N bar
The necessary flexible wires
Connectors (AD 95 for phase connection, AD 70 for PE
and N connection).
Installation instructions
Can also be used in a TN-C system.
SVA
Buried cable > 200 m
SCA
Lightning conductor
SCA
Overhead line